Teledyne Simtronics GD10P CO2 Infrared Point Gas Detector
The GD10P-CO2 uses state-of-the-art IR gas measurement to give a
fast,
reliable response. The GD10P has set the standard for gas
detection in the
areas of safety, stability and low maintenance.
The GD10P comes with a 5-year warranty. The GD10P-CO2 has been
designed with
features that provide an effective response to the detection of
CO2 in a
wide range of industrial environments, from boiler plant rooms
to offshore
petrochemical installations.
The GD10P-CO2 differs from all other point infrared gas detectors
because it
utilises silicon-based solid-state sources.
The complete optomechanical design and construction is so stable
that an
ultra-fast speed of response can be achieved whilst providing
unparalleled
service life and detector stability, thus saving on maintenance
and service
costs.
Offering the longest combined detector and IR source warranty on
the market.
Supplied with worldwide hazardous area approvals. An industry
standard HART
interface is used for configuration of special fault levels as
well as
access to extended maintenance data.
Features
- Solid state IR sources (SimSource) for superior long-term
performance
compared to filament lamps.
- Dual-layer weather protector (No mesh, gauze, hydrophobic
filters or
sinters = No delay, no failure on demand).
- Low power consumption reduces the load on the UPS.
- Independently heated mirror and lens for high-performance
detection in
rough environmental conditions.
- The integral termination compartment enables reduced
installation time,
and the unit is ready out of the box.
- No recalibration is required; it monitors and accounts for
all changes
in the optical path, thanks to its true dual-path,
double-compensation
optical design.
Other Versions
- GD10P Combustible gas detector
- The PE model detects flammable gas in large volumes of air
Order Information
GD10P Detector Range
| ATEX / IECEx Approved |
| Model |
Description |
| GD10-P00-23AN-0XH-00 |
CO2 10,000 ppm, SS316L, ATEX, IECEx, HART
|
| GD10-P00-23BH-0XH-00 |
CO2 3% Vol., SS316L, ATEX, IECEx, HART |
| GD10-P00-23BC-0XH-00 |
CO2 5% Vol., SS316L, ATEX, IECEx, HART |
| GD10-P00-23BD-0XH-00 |
CO2 10% Vol., SS316L, ATEX, IECEx, HART |
| GD10-P00-23BJ-0XH-00 |
CO2 25% Vol., SS316L, ATEX, IECEx, HART |
| GD10-P00-24BC-0XH-00 |
CO2 5% Vol. (CH4 immune), SS316L, ATEX,
IECEx |
| GD10-P00-24BG-0XH-00 |
CO2 100% Vol. (CH4 immune), SS316L, ATEX,
IECEx |
| CSA Approved |
| Model |
Description |
| GD10-P00-23AN-0BH-00 |
CO2 10,000 ppm, SS316L, CSA, HART |
| GD10-P00-23BH-0BH-00 |
CO2 3% Vol., SS316L, CSA, HART |
| GD10-P00-23BC-0BH-00 |
CO2 5% Vol., SS316L, CSA, HART |
| GD10-P00-23BD-0BH-00 |
CO2 10% Vol., SS316L, CSA, HART |
| GD10-P00-23BJ-0BH-00 |
CO2 25% Vol., SS316L, CSA, HART |
| GD10-P00-24BC-0BH-00 |
CO2 5% Vol. (CH4 immune), SS316L, CSA |
| GD10-P00-24BG-0BH-00 |
CO2 100% Vol. (CH4 immune), SS316L, CSA |
| UL Approved |
| Model |
Description |
| GD10-P00-23AN-0CH-00 |
CO2 10,000 ppm, SS316L, UL |
| GD10-P00-23BH-0CH-00 |
CO2 3% Vol., SS316L, UL |
| GD10-P00-23BC-0CH-00 |
CO2 5% Vol., SS316L, UL |
| GD10-P00-23BD-0CH-00 |
CO2 10% Vol., SS316L, UL |
| GD10-P00-23BJ-0CH-00 |
CO2 25% Vol., SS316L, UL |
| GD10-P00-24BC-0CH-00 |
CO2 5% Vol. (CH4 immune), SS316L |
| GD10-P00-24BG-0CH-00 |
CO2 100% Vol. (CH4 immune), SS316L |
| Accessories |
| Model |
Description |
| 499-811176 |
Adapter plate |
| 599-811547 |
Adapter plate GD100-GD10P |
| Installation |
| Model |
Description |
| AS053-X |
SS316L Mounting Plate |
| AS057-X |
U-bolts for 2″ pipe |
| AS058-X |
U-bolts for 2.5″ pipe |
| AS049 |
Wall Mount Adapter |
| 499-811938 |
Duct Mount Kit |
| Protection |
| Model |
Description |
| 499-813397 |
Mosquito Net |
| 499-815712 |
Sunshade |
| Maintenance |
| Model |
Description |
| 599-818154 |
Gas Test Socket |
| 499-810874 |
Sample Flow Housing |
| 140-816580 |
Hand-held Terminal |
| TLU600 |
IR Remote Control Unit |
| TLH710 |
HART Remote Control Unit |
| Display |
| Model |
Description |
| GD10P-DISPLAY-A-ATEX |
Loop-powered Indicator, ATEX |
| GD10P-DISPLAY-A-CSA |
Loop-powered Indicator, CSA |
| GD10P-DISPLAY-X-ATEX |
SS Indicator, ATEX |
| GD10P-DISPLAY-X-CSA |
SS Indicator, CSA |
| R-5000AL-2 |
Display Module Aluminium |
| R-5000SS-2 |
Display Module Stainless Steel |
| Spares |
| Model |
Description |
| 373-901337 |
Terminal GD10P |
| 499-810913 |
Front Cover GD10P |
| 599-810646 |
Test Nipple |
| 599-904176 |
Protective Cap |
General Specifications
| Detection Method |
IR-absorption, dual wavelength, dual path |
| IR Source |
Solid state IR source, 50Hz flash |
| Gases Detected |
CO2 |
| Self-test |
Continuous |
| Calibration |
Factory set, no field recalibration |
| Configuration |
HART (response time, fault levels) |
Performance
| Accuracy |
±5% FS (0-50%), ±7% FS (50-80%) |
| Response Time |
T20 = 1 sec (0.3 sec), T50 = 2.5 sec (0.7 sec), T90
= 6 sec (1.6 sec) |
Output Signal
| Standard |
Current source 4–20 mA, max load 500 ohm |
| Option |
Current sink 4–20 mA |
| HART |
Maintenance and configuration |
| Detector Warnings |
Early clean optics – Pre warning (2 mA)
Dirty optics – Dirt accumulation (1 mA)
Detector failure – Internal fault (0 mA)
|
Electrical
| Power Supply |
24V DC (18–32V DC) |
| Power Consumption |
Approx. 3.5 W |
| Connection |
3 wires (0.5mm² – 2.5mm²) |
| Cable Entry |
M20 Exe cable gland |
Temperature Range
| Storage |
-40°C to +70°C |
| Operating |
-40°C to +60°C |
| Humidity |
100% RH |
Explosion-Proof Housing
| Protection |
IP66/IP67 |
| Material |
Stainless Steel (SIS2343 / ASTM316) |
| Weight |
Approx. 2.9 kg |
| Dimensions |
251 x 104 x 105 mm (9.89 x 4.1 x 4.13 in) |
Warranty
| Instrument |
5 Years |
| IR Source |
15 Years |
Approvals
| ATEX / IECEx / INMETRO |
II 2G Ex de IIC T6 Gb |
| CSA |
Ex de IIC T6 |
| Classification |
Class I, Division 2, Groups A, B, C, D |
| Other |
SIL2 (Software SIL3), ABS, MED |
Versions
| Standard Ranges |
10000ppm (1%), 3%, 5%, 10%, 100% |
| Note |
0–100% volume compensated for Methane interference
|
Front Cover Options
| Weather Protection |
Standard point detector |
| Sample Flow Housing |
Sampling systems and testing |
| Duct Mount Kit |
Through-wall installation |
Accessories
| Mosquito Net |
Extra insect protection |
| Sun Shade |
Protection from extreme radiation |