Crowcon Vortex Gas Control System
The Oldham MX 43 by Teledyne is a flexible gas detection system controller
that continuously monitors, measures, and controls gas hazards, conforming
to the Functional Safety Performance Level 1 standard. The MX 43 manages
both digital lines and analogue channels. Incorporating digital technology
allows up to 32 detectors to be distributed on eight lines or 16 detectors
across four lines.
Featuring a multi-language, backlit LCD display, customisable by the user, 1
to 16 channels can be viewed simultaneously. Access to operation menus is by
five smart keys, with one audible alarm accept/reset button.
An optional 4GB USB module provides two years of storage or eighteen months
for a controller equipped with 32 detectors. The user can set sampling rates
from 2 seconds to 15 minutes, recording all events in real time (alarms,
faults, alarm resets, calibration). The USB allows firmware updates and
controller configuration.
Com 43 software enables controller programming and is compatible with any MX
43 controllers already in use. Controller parameters are configured on a PC
and transferred to the MX 43 using a USB cable.
Full functions can be accessed
- Configuration of measurement channels.
- Simplified relay programming.
- Up to 5 on-board functions: OR, AND, NOR, NAND, VOTING.
- Advanced management of audible alarms with timer options (holding time,
automatic acknowledgement, reactivation, evacuation).
Programming functions
- Graphic display for easy relay programming.
- Copy-paste function saves time by preventing programming errors from one
sensor to the next.
- Verification/validation feature to avoid programming errors.
- Access a pre-programmed gas monitor library that conforms to industry
standards.
Benefits and features
- Digital inputs up to eight, RS-485, 9600 baud and Analogue inputs up to
eight, 4 to 20 mA for measurement.
- Buzzer 77dB @ 30cm.
- Ingress protection IP55 (wall-mounted), IP31 (rack).
- Two extra MOSFET outputs for driving the audible and visual alarms.
- Five programmable events per detector (1 to 3 alarms, underscale,
overscale) and a fault event.
- Front-panel LEDs provide a quick, basic overview of the installation.
- Remote modules (cost savings on wiring installation).
- Up to 32 fully programmable relays (OR, AND, NAND, NOR, Voting
functions).
Approvals
- EMC, according to EN50270.
- MED, according to Directive 96/98/EC.
- ATEX, EN 50271, and metrological performances according to EN
60079-29-1.
- CSA, pending.