The SENTRY io Controller provides an easy-to-use platform for nearly any application and skill level.
Modern touchscreen HMI supports intuitive setup, operation, and troubleshooting workflows.
Guided setup and auto-recognition of MSA and General Monitors flame and gas detectors through HART saves valuable time during setup and configuration.
10211156 CONTROLLER,SENTRY io,8PT,32RLY,0AO,M20
10211157 CONTROLLER,SENTRY io,8PT,32RLY,8AO,M20
10211160 CONTROLLER,SENTRY io,16PT,32RLY,0AO,M20
10211161 CONTROLLER,SENTRY io,16PT,32RLY,16AO,M20
10246522 Analogue Output Module, 24VDC, 6 Channel
10246523 Buzzer
10246524 Display, 24VDC, LCD
10246525 Expansion Module
10246527 Fan, DC, Brushless, 24VDC
10246529 Memory Card, Micro SD, 16GB
10246526 Power Supply, 24V, 10A
10246528 Relay Module, 24VDC, 8 I/O
| System Specifications | |
|---|---|
| Auto-recognized Products (Ez-id, Via Hart) | ULTIMA® X5000 Gas Monitor, ULTIMA X Gas Monitor, PrimaX® Gas Monitor Series, Senscient ELDS™ Open Path |
| Compatible Products | MSA, General Monitors, and analog/discrete third party instruments |
| Display | 7” (178 mm) touchscreen LCD |
| Languages | English, French, German, Italian, Portuguese, Spanish, Chinese |
| Functional Indicators | System Normal, Alarm, and Fault (located on touchscreen) |
| Pre-programmed Functions | Remote Reset, Remote Silence dry contact inputs |
| Remote Access Capability | Remote display is available option through Ethernet connection |
| Digital Communications Supported | Modbus TCP/IP, Modbus RTU (optional), EtherNet/IP/DLR (consult factory for setup) |
| Program Storage / Retrieval / Back Up Options | USB or SD card |
| Hazardous Area Classification | Class I, Div 2 (Groups A, B, C, & D) |
| Warranty | 2 years |
| Cloud Enabled | Yes |
| Approvals | cFMus (for electrical safety, hazardous locations and gas performance), ATEX and EMC Directives, IECEx, UKCA, CE marking. Gas performance to the following standards: FM 6340, FM 6320, ANSI/ISA 92.00.01, ANSI/ISA 92.04.01, ANSI/FM/CSA/IEC/EN 60079-29-1, EN 50104. |
| Electrical Specifications | |
| Input Power | 85-264 VAC, 50-60 Hz (auto-switching input) |
| Power Consumption | 1.4 Amps @ 24 VDC (controller alone) |
| Power Capacity | 8.6 Amps @ 24 VDC (max field device power available at 24 VDC) |
| Maximum Number Of Inputs |
16 analog or 16 analog with HART gas detectors 6 discrete dry contact inputs |
| Input Types Supported | Analog with HART, discrete dry contact inputs |
| Maximum Number Of Outputs | 56 relays, 16 analog outputs |
| Output Types Supported | Relays, analog outputs |
| Output Relay Contacts | |
| Maximum Load | 2 Amp @ 240 VAC resistive, 2 Amp @ 30 VDC resistive |
| Minimum Load | 1 mA @ 5 VDC resistive |
| Ground Fault Monitoring | No |
| Environmental Specifications | |
| Temperature Range | -4°F to 149°F (-20°C to 65°C) |
| Storage Temperature Range | -4°F to 149°F (-20°C to 65°C) |
| Humidity | 20% to 95% RH, non-condensing |
| Mechanical Specifications | |
| Housing | Fiberglass, NEMA 3X, IP65 |
| Dimensions | 22” x 17.62” x 9.5” (559 x 448 x 241 mm) |
| Weight | 44 lb. (20 kg), based on a 16 point / 56 relay unit |
Get in touch with us to see how we can help you with your project